PCME - Passionate about Particulate


PCME VIEW Ex 800 / 820


Sensor

316 stainless

temperature range -20°C to +250°C, option to +400°C

RS485 (Modbus) output to control unit

24VDC power supplied via control unit

IP65 die-cast aluminium LM6M enclosure

ATEX/IECEx category 1G/2G/3G/1D/2D/3D for gas zones 1, 2, 3 and dust zones 20, 21, 22

Intrinsically safe design, with isolating spur between sensor and control unit to ensure no current can circulate in the ground system

Air Filter and Regulator assembly for plant instrument air (air purge typically not required for most applications)
Control Unit

Single Channel Entry and Standard units, or 1-16 Channel PLUS unit for extended sensor networking capability

Industrially hardened display screen and enclosure with icon driven, multilingual menus for intuitive user interface

Data logging: Simultaneous recording of pulse data (for arrestment plant cleaning diagnostics), short term data (for process control), long term data (for external emissions reporting), and Alarm log for up to 500 alarming events

Alarming: Local (audible and visual), and via 4 x user selectable relay outputs (PLUS), expandable via 'ROM' module

Ethernet (Modbus TCP) connectivity for industrial network integration

4 x 4-20mA and 1 x RS485 (Modbus RTU) outputs (PLUS), expandable via 'AOM' module

External Inputs: Accepts input data from external devices (e.g. for temp and O2 normalisation, plant off indication, bag cleaning reference, multiple calibrations) via digital and 4-20mA inputs, expandable via 'AIM' module

Pulse log review to diagnose location of leaking bags